Principle and constitution of a ground source heat pump water heater was presented, a number of experiments were carried out. Experiment results showed that this heat pump water heater was very efficiency in energy saving. Its energy efficiency ratio EER could reach 3.1-3.2. Its performance was so steadily that the change range of EER was only 3.1-3.18 while outdoor air temperature changed from 0°C to 10°C. Besides, characteristic of ground heat-exchanger was analyzed. The outlet water temperature decreased from 16°C to 13.3°C in the first 35 min, and it increased slightly to 13.7°C in the later 30 min. The principle of this phenomena was explained.