Abstract
Principle and constitution of a ground source heat pump water heater was presented, a number of experiments were carried out. Experiment results showed that this heat pump water heater was very efficiency in energy saving. Its energy efficiency ratio EER could reach 3.1-3.2. Its performance was so steadily that the change range of EER was only 3.1-3.18 while outdoor air temperature changed from 0°C to 10°C. Besides, characteristic of ground heat-exchanger was analyzed. The outlet water temperature decreased from 16°C to 13.3°C in the first 35 min, and it increased slightly to 13.7°C in the later 30 min. The principle of this phenomena was explained.
| Original language | English |
|---|---|
| Pages (from-to) | 125-130 |
| Number of pages | 6 |
| Journal | Huagong Xuebao/Journal of Chemical Industry and Engineering (China) |
| Volume | 57 |
| Issue number | SUPPL. |
| Publication status | Published - Dec 2006 |
| Externally published | Yes |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Energy efficiency ratio
- Energy saving
- Ground source heat pump
- Water heater
Fingerprint